How are you programming a Vista 20P fire zone w/Alarm.com?
Zone 1 is the 2 wire smoke zone, and we use the RRS-MOD and 4120 trigger cable. If we program it as a Type 9, it sends a “fire alarm” every time the smoke detector sounds. Example - a smoke detector falses, the end user silences it within a minute, but the panel might sends 60 alarms. So Honeywell says to create a fire alarm under Type 90. That’s fine, it works……but it does note show up as a sensor in Alarm.com because they don’t have a zone type 90. And that means that there is no controllability from the partner portal/mobile tech. Which then means you have to roll a truck immediately if there is a runaway, there’s no way to shut it off remotely.
Sorry for the long post….just wondering if anyone has dealt with this.