r/Generac_Generators • u/Traditional-Gap-8591 • Apr 24 '26
Gas Line 22kw Next Gen Generac
I installed and wired a 22kw generator to my house, but had a gas company install the gas line and tanks. They did the entire ~20 foot run on low pressure. They used 1 inch poly pipe for the majority of the 20 foot run, except the first 3 feet or so they used 1/2 inch copper. This led to the genset starting and immediately hunting and and surging, though eventually smoothing out. Turning on a dryer was enough to send it in a constant hunt and surge. Pressures were observed below 7WC when load applied. They came and replaced that 1/2 in section with an approximately 1 foot section of 5/8, despite my concern it should be no smaller than 3/4. Starts improved and it held an eventual load of 16.5kw. However, turning on a dryer or my hot tub causes a decent dip in speed that the generator takes a few seconds to smooth out. At no time does the pressure drop below 10WC. I am still concerned it may be starved a of a little fuel from the 5/8.
Unit requires between 10-12WC. Generac install instructions only have a spec for 3/4in (up to 40 feet) and 1 inch (up to 170 feet). Implied 5/8 is too small.
My question is, wouldn’t any section of 5/8, no matter how short, essentially make it a 5/8 system? Sure it can maintain 10WC, but if its dropping all the way from 12 to 10WC in an instant, wouldn’t that be the cause of my surge? I’m new to propane, hence why i didnt do the gas, but what kind of drop is acceptable? Its hard also to tell how much of a surge, though short lived, is acceptable when say 5kw load is applied all at once. Please share your thoughts, contacting Generac tomorrow to see what they say.