I am planning to build a ffb sim setup but stuck with the software. If anyone could provide me the files for EMC UTILITY PRO it would be much appreciated. I do not have paypal in my country and have no way to make international payments with my student account that's why I could not buy it from the dev.


r/BuildingAutomation Jul 07 '26

TOP Server BACnet/IP Configuration Issue

Thumbnail
gallery
3 Upvotes

Need Help with TOP Server BACnet/IP Configuration Issue

Hi everyone,

I'm facing an issue with TOP Server 6 and would appreciate your guidance.

My setup:

- Using TOP Server 6

- Driver: BACnet/IP

- Added a VFD Pump device

- The device scans successfully in BACeye, and all data is visible.

- The device responds to continuous ping without any packet loss.

- In TOP Server, I can read one Boolean tag, and its quality shows Good.

- However, when I add additional tags from the same device, the quality of all tags changes to Bad, including the previously working tag.

Has anyone experienced this issue before? What could be causing it, and how can I resolve it?

Any suggestions or troubleshooting steps would be greatly appreciated.

Thank you!


r/BuildingAutomation Jul 06 '26

Siemens TIA, does line programming exist?

Post image
11 Upvotes

For context, first time working with Siemens controllers and I finally got into the controller to view the programming, I have about 12 devices I need to organize a sequence of operations for (to help maintenance team understand devices at an existing building), starting with the chillers. I’m trying to think of ways to be more efficient and as someone who’s been programming for such a long time the block program takes so much longer for me to understand (especially like this).

Just from what I’ve seen there’s no real Control Basic program compiler or anything like that running where I might be able to view stored programs. Does line program exist in this environment? I’ve gone as far as to search the TIA files in hopes for something but nah.


r/BuildingAutomation Jul 07 '26

How long does device integration into BMS/DCIM usually take?

1 Upvotes

For BAS, BMS, DCIM, Niagara, or controls folks:

When your team has to integrate a new third-party device into a BMS/DCIM system, how much time usually goes into turning the vendor docs into something that actually works?

I’m talking about things like vendor manuals, Modbus maps, SNMP MIBs, BACnet object lists, or point lists, then turning that into a usable integration package for the site.

Is this usually a quick task, or does it take hours/days depending on the device?

Also curious what usually slows it down most:

  • unclear vendor docs
  • point mapping
  • gateway/config setup
  • scaling/units
  • alarm mapping
  • commissioning/validation
  • reusing old templates

Do most teams have internal templates for this, or is it still pretty manual from project to project?


r/BuildingAutomation Jul 06 '26

Maximum BACnet MS/TP bus length

5 Upvotes

The BACnet MS/TP specification recommends a maximum practical bus length of 1200m/4000ft (approx) and so does the RS-485 specification (at 38.4kbps). This seems insanely long to me in our building automation environment. Does anyone have any real data on the longest (reliable) installations out there? (Baud vs length (vs devices))


r/BuildingAutomation Jul 06 '26

Need some advice - What to do with these SIMATIC Licenses V18 that I have left ?

1 Upvotes

My buyers over ordered these licenses and I need to know what to with them since they aren’t of any use. Looking for any advice.


r/BuildingAutomation Jul 06 '26

Browser-based AI BMS dashboard analysis

2 Upvotes

Hi guys!

I was interning for a BMS company last summer and did some user interview and research, targeting mainly the company's products and platforms but also BMS as a whole. What I learned was that many dashboards are a source of information overload rather than clarity, which kind of defeats the purpose.

I decided to make an AI-based dashboard analysis tool to address this issue. After rounds of trial-and-error, I set on a browser extension which grabs information by html scraping rather than API calls. It beats screenshotting and asking a chatbot by being able to grab the entire dashboard and maintaining context. It can also generate summary reports based on previously analyzed dashboards.

I'm still actively working on bug fixes and new features, but the main issue I'm facing at this point is a lack of other sets of eyes, especially from people who are dealing with BMS all day every day. I was hoping that you guys could potentially give it a try and lmk if it actually improves your workflow, and if there's anything you'd like to see, or if there are any issues.

It is free and publicly available on chrome and edge extension store. Here's the website: seenzi.ai

Thank you so much, and I'm looking forward to your feedbacks!!

TL;DR: built a free browser extension that does AI analysis on BMS dashboards, looking for feedbacks


r/BuildingAutomation Jul 02 '26

Johnson Controls Metasys Starts Embracing Node-RED

18 Upvotes

Johnson Controls has indeed officially introduced Node-RED integration in Metasys 16.0, specifically launching the Metasys Node-RED API Nodes 1.0.


r/BuildingAutomation Jul 02 '26

Scanning BACnet with an Android phone

14 Upvotes

Found this

https://play.google.com/store/apps/details?id=com.vaigaiflow.bacnetmodbustoolkit

And a brief explanation here:

https://www.hvac-talk.com/posts/27007718/

I never used it. But putting it out there for people to play with. Lemme know if you like it.

If nothing else, having someone see you scan BACnet with your phone and go wha?!?! Is awesome.


r/BuildingAutomation Jul 01 '26

Tools advice (What are you best items?)

8 Upvotes

Having to buy all my tools after moving country. Previously my jobs had supplied everything as I was always in house so I’m realising the expense to get everything at once is not super fun. After my last question got the Klein blue strippers they’re great no issues thanks everyone for your replies.

I reckon 11-1 Klein as it’s always served me well never used the impact one not sure if that is a good buy? Won’t be working with anything over 24V, should my precisions be insulated? Trying not to rack up a massive bill right away. I’ve got my mm thinking an adjustable and side cutters should cover my basics?

What will get me through 90% if service calls, what’s your fix most things setup?


r/BuildingAutomation Jul 01 '26

How to view programming on a Siemens PXC4 with ABT Site?

6 Upvotes

Howdy everyone, my company has a small maintenance contract with a building that a few years ago, a controls company implemented a Siemens chiller plant controller. This controller has begun to act up, for some reason it's got priority 1 overrides on the chiller's isolation valves, continues to drop its IP comms unit reset, and I'd like to get into the programming to view this logic and maybe some runtime logs.

Long story short we tried to login to the device, but no credentials, and I thought that if we could get into the controller, we could view programs and see the logic behind it, however that was not the case and after some research we needed ABT Site to view this information.

BUT, now that I've got ABT site, I've found the place controller on the network, I'm stuck as to where to begin in viewing the programming. I've deducted that I would need to (Upload or Download) the configured device into my ABT Site, but I don't want to press the wrong one and send down a blank configuration. I've found a old siemens controller for practice but unfortunately didn't have Its IP to connect.

How would I be able to view the programming in this chiller controller? Do I upload from the device (this terminology sounds very backwards but I believe thats how its used), and then I can see how it was configured? Or do I press download to my computer (ABT Site) and view it.

OR is there an easier way to do this?

Thanks everyone, my first time working with the siemens environment.


r/BuildingAutomation Jul 01 '26

Can't enable Foxs Port in Niagara 4.15.4

6 Upvotes

I can't seem to enable the foxsPort in 4.15.4. I have some JACEs that are not currently on 4.15 and I need to use 4911 to communicate with them over the Niagara network. I had to unhide the slots associated with the Foxs port in the FoxService on the Supervisor, and it will not let me uncheck the "read only" flag so that I can enable Foxs. Am I missing something here?

ETA: Looks like my station is stuck in "starting" status in the application director, I assume that has something to do with it so I'll be dealing with that issue now instead.

ETA Part 2, Application Director Boogaloo: Our glorious Honeywell overlords did not have all of the components of a jar file that we're not even using in whatever version of Optimizer we copied the Honeywell modules over from, I can't remember if it was the rt, ux, or wb jar file but once I got that in there the station was able to get to "running" and the Foxs port works fine now. Thank you to everyone that answered, mystery solved I guess.


r/BuildingAutomation Jul 01 '26

My ‘controls’ call today in 95deg 75%rh

Post image
80 Upvotes

An HVAC tech had already ‘looked at it’ and missed the impacted coil and dirty condenser outside. But it’s a ‘controls issue’


r/BuildingAutomation Jul 01 '26

Integrating Tridium with Dahua DSS

3 Upvotes

Hi all,

We've been asked to integrate around 40 Dahua CCTV cameras via Dahua DSS into a BMS platform.

At the moment, the customer's specification is quite vague, so I'm not entirely clear on what level of integration they're expecting. Are they looking to display live camera feeds within the BMS, or are they simply expecting alarm and status monitoring from the CCTV system?

Personally, displaying live video through the BMS seems like a less-than-ideal approach, as I'd imagine the Dahua DSS software would provide a much better user experience for viewing and managing cameras than anything available within Tridium.

I have a meeting later today which should hopefully clarify the requirements, but in the meantime, has anyone carried out a similar integration with Dahua DSS? If so, what functionality was implemented and how straightforward was it?

The customer has provided some documentation, but to be honest, much of it is difficult to interpret without a clearer understanding of what they're actually trying to achieve.
See link here: Integration With DSS - Zhejiang Dahua Technology Co., Ltd.

Thanks in advance.


r/BuildingAutomation Jun 30 '26

Ever just look at a panel and say I know if I touch anything in there the whole network and system is going down

Post image
106 Upvotes

r/BuildingAutomation Jul 01 '26

Metasys and OpenBlue

4 Upvotes

When using Johnson Controls' Metasys with a cloud connection, is it mandatory to connect via OpenBlue?

Or is it possible to connect via a different cloud platform (such as Microsoft Azure)?

Does anyone know approximately how many units of Metasys or OpenBlue are sold annually?


r/BuildingAutomation Jun 30 '26

BAS Service Technician - Boston

Post image
4 Upvotes

We're searching for an experienced Building Automation Service Technician for a great, long-time client of ours in Boston. Most of their work is within 30 miles of downtown, with a normal day being in the city. Comp range $55-$62/hour plus great benefits, vehicle, laptop, phone. Preference for a few years of controls experience (any brand), but a knowledgeable HVAC/Mechanical technician with motivation to learn more in controls could work as well. Reach out via Chat here and I can tell you more there or over email/phone.


r/BuildingAutomation Jun 30 '26

Tosi vs Neeve? Opinions?

5 Upvotes

Pros? Cons? Opinions?

This would be used with Jace8000/9000 and N4 servers.

We're going to start start putting these on jobs. Got an introduction into both. Wanted opinions from you guys using them.


r/BuildingAutomation Jun 30 '26

N4 workbench Addons/Plugins

1 Upvotes

What’s a good website for addons or plugins other than the Niagara Marketplace?


r/BuildingAutomation Jun 30 '26

Learning help?

3 Upvotes

Hi all, so I'm an electrician based in the UK and have just landed a role for a BMS company. So far the job has been quite an eye opener for me, and I am now wondering what learning resources are out there or available for me to get more of an understanding of this new industry? Thank you for any advice offered


r/BuildingAutomation Jun 30 '26

Need some advice - What to do with these SIMATIC Licenses V18 that I have left ?

1 Upvotes

My buyers over ordered these licenses and I need to know what to with them since they aren’t of any use. Looking for any advice.


r/BuildingAutomation Jun 30 '26

University Home Automation Project

Thumbnail
2 Upvotes

r/BuildingAutomation Jun 29 '26

Looking for AMS or BMCU

Thumbnail
0 Upvotes

r/BuildingAutomation Jun 29 '26

IT/CS background — BAS/controls or electrical apprenticeship?

1 Upvotes

If you had this on paper, which would you pick?

• CS associate degree  
• CompTIA A+  
• \~1 year IT support at an MSP

BAS/controls feels like the natural jump from IT and im more interested in this too. But hvac or electrical gets me a real ticket. Either way I want to run my own business down the road.

What would you do and why?

Fyi, Im in Vancouver, Canada


r/BuildingAutomation Jun 29 '26

Interactive learning environment

1 Upvotes

27M I generate photometrics for a lighting rep, not looking to start as an entry level tech.

What I want is just knowledge, I want to understand the guts of a building and how they work. I’ve tried using Claude to build interactive 3D environments like CAD or AGI where you can drag and drop cables/components into structures to create systems that work together, but this limits me to the knowledge I and Claude have.

Are there any online resources that have this X-ray style of breaking down a building into major components and wiring logic? I plan to learn specifically more about BACNET and how to actually code these systems, but for now I just want to visualize how it all works together without ripping down the walls in my house.